Additional parameter data 405
76.30 Start point 1 Real 0…32767 rpm/Hz 1 = 1 unit
76.31 Start point 2 Real 0…32767 rpm/Hz 1 = 1 unit
76.32 Start point 3 Real 0…32767 rpm/Hz 1 = 1 unit
76.41 Stop point 1 Real 0…32767 rpm/Hz 1 = 1 unit
76.42 Stop point 2 Real 0…32767 rpm/Hz 1 = 1 unit
76.43 Stop point 3 Real 0…32767 rpm/Hz 1 = 1 unit
76.55 Start delay Real 0.00…12600.00 s 100 = 1 s
76.56 Stop delay Real 0.00…12600.00 s 100 = 1 s
76.57 PFC speed hold on Real 0.00…1000.00 s 100 = 1 s
76.58 PFC speed hold off Real 0.00…1000.00 s 100 = 1 s
76.59 PFC contactor delay Real 0.20…600.00 s 100 = 1 s
76.60 PFC ramp acceleration time Real 0.00…1800.00 s 100 = 1 s
76.61 PFC ramp deceleration time Real 0.00…1800.00 s 100 = 1 s
76.70 PFC autochange List 0…13 - 1 = 1
76.71 PFC autochange interval Real 0.00…42949672.95 h 100 = 1 h
76.72 Maximum wear imbalance Real 0.00…1000000.00 h 100 = 1 h
76.73 Autochange level Real 0.0…300.0 % 10 = 1%
76.74 Autochange auxiliary PFC List 0…1 - 1 = 1
76.81 PFC interlock 1 List 0…10 - 1 = 1
76.82 PFC interlock 2 List 0…10 - 1 = 1
76.83 PFC interlock 3 List 0…10 - 1 = 1
76.84 PFC interlock 4 List 0…10 - 1 = 1
76.95 Regulator bypass control Binary
src
---
77 PFC maintenance and monitoring
77.10 PFC runtime change List 0…5 - 1 = 1
77.11 Pump/fan 1 running time Real 0.00…42949672.95 h 100 = 1 h
77.12 Pump/fan 2 running time Real 0.00…42949672.95 h 100 = 1 h
77.13 Pump/fan 3 running time Real 0.00…42949672.95 h 100 = 1 h
77.14 Pump/fan 4 running time Real 0.00…42949672.95 h 100 = 1 h
90 Feedback selection
90.03 Load speed Real -32768.00...32768.00 rpm 100 = 1 rpm
90.52 LoadSpeed filter time Real 0...10000 ms 1 = 1 ms
90.61 Gear numerator Real -2147483648...
2147483648
-1 = 1
90.62 Gear denominator Real -2147483648...
2147483648
-1 = 1
90.99 Load speed unit List - rpm 1 = 1
95 HW configuration
95.01 Supply voltage List 0, 2 - 1 = 1
95.02 Adaptive voltage limits List 0…1 - 1 = 1
95.03 Estimated AC supply voltage Real 0…65535 V 1 = 1 V