Parameters 267
60.50 DDCS controller
drive type
In ModuleBus communication, defines whether the drive is of
the “engineered” or “standard” type.
Note: This parameter cannot be changed while the drive is
running.
ABB
engineered
drive
ABB engineered
drive
The drive is an “engineered drive” (data sets 10…25 are
used).
0
ABB standard drive The drive is a “standard drive” (data sets 1…4 are used). 1
60.51 DDCS controller
comm port
Selects the DDCS channel used for connecting an external
controller (such as an AC 800M).
Not in use
Not in use None (communication disabled). 0
Slot 2A Channel A on FDCO module in slot 2. 2
Slot 2B Channel B on FDCO module in slot 2. 5
RDCO CH 0 Channel 0 on RDCO module (with BCU control unit only). 10
XD2D Connector XD2D. 7
60.52 DDCS controller
node address
Selects the node address of the drive for communication with
the external controller. No two nodes on-line may have the
same address.
With an AC 800M (CI858) DriveBus connection, drives must
be addressed 1…24; with an AC 80 DriveBus connection,
drives must be addressed 1…12. Note that the BusManager
function must be disabled in the DriveBus controller.
With optical ModuleBus, the drive address is set according to
the position value as follows:
1. Multiply the hundreds of the position value by 16.
2. Add the tens and ones of the position value to the result.
For example, if the position value is 101, this parameter must
be set to 1×16 + 1 = 17.
1
1…254 Node address.
60.55 DDCS controller
HW connection
Selects the topology of the fiber optic link with an external
controller.
Star
Ring The devices are connected in a ring topology. Forwarding of
messages is enabled.
0
Star The devices are connected in a star topology (for example,
through a branching unit). Forwarding of messages is
disabled.
1
60.56 DDCS controller
baud rate
Selects the communication speed of the channel selected by
parameter 60.51 DDCS controller comm port.
4 mbps
1 mbps 1 megabit/second. 1
2 mbps 2 megabit/second. 2
4 mbps 4 megabit/second. 4
8 mbps 8 megabit/second. 8