EasyManua.ls Logo

ABB ACS880-01 - Page 119

ABB ACS880-01
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
118 Electrical installation – North America
UL
NEC
Connecting the power cables
Connection diagram
ADrive
1 For alternatives, see section Selecting the supply disconnecting device on page 51.
UDC-
UDC+
L1 L2 L3
T1/U T2/V T3/W
L1 L2 L3
PE
PE
U1
V1
W1
3 ~ M
1
2
A
R+R-
L1 L2 L3
T1/U T2/V T3/W
L1 L2 L3
PE
PE
U1
V1
W1
3 ~ M
1
2
A
6
3
3
5
34
DriveA
For alternatives, see section Selecting the main supply disconnecting device (page 61).
1
Use a separate grounding PE conductor inside the conduit or a grounding cable, if the
conductivity of the conduit does not meet the requirements for the PE conductor (see Se-
lecting the power cables (page 69)).
2
Note: If the cross-section of the Cu PE conductor is less than 8 AWG, install a second Cu
PE conductor of the same cross-sectional area as the original PE conductor. Alternatively,
you can use a Cu PE conductor with at least 10 mm2 cross-section. See Selecting the power
cables (page 69).
Make sure of a correct grounding of the conduit at the cable entry. Ground the other end of
the conduit and grounding conductor (if used) at the distribution board.
3
Make sure of a correct grounding of the conduit at the cable entry.4
Make sure of a correct grounding of the conduit at the cable entry.5
External brake resistor (if used), see chapter Resistor braking (page 263).
6
Note: Do not use an asymmetrically constructed motor cable for motors above 30 kW. Connecting
its fourth conductor at the motor end increases bearing currents and causes extra wear.
Electrical installation North America 119

Table of Contents

Other manuals for ABB ACS880-01

Related product manuals