Grounding ter-
minals
L1, L2, L3, T1/U, T2/V, T3/WCable entriesFrame
lbf·ft
Max.
wire
size
lT (Wire screw)Wire sizeØ *
pcs
AWGin.lbf·ftM…kcmil/AWGin.
7.22×1.1829.5M102 × (1/0…300
MCM)
1.774R8
350
MCM
7.22×1.1851.6M122 × (3/0…400
MCM)
2.134R9
350
MCM
R-, R+/UDC+ and UDC- terminalsCable entriesFrame
lT (wire screw)Wire sizeØ *
pcs
mmlbf·ftM…kcmil/AWGin.
0.310.44-18…100.671R1
0.310.44-18…100.671R2
0.391.25-20…60.831R3
0.702.4-20…20.941R4
1.184.1M810…2/01.261R5
1.1814.8M84…3/01.381R6
1.1822,1M104…300 MCM1.691R7
1.1829.5M102 × (1/0…300
MCM)
1.772R8
1.1851.6M122 × (3/0…400
MCM)
2.132R9
* maximum cable diameter accepted. Cable connector inside diameter: 3/4” (frames R1
and R2), 1” (R3). For the entry plate hole diameters, see chapter Dimension drawings.
** 525…690 V drives
UL listed cable lugs and tools
Crimping toolCompression lugWire size
No. of crimpsTypeManufacturerTypeManufacturerkcmil/AWG
1TBM4SThomas &
Betts
E10731
54136
Thomas &
Betts
6
TBM45S
1MY29-3BurndyYAV6C-L2Burndy
2ILC-10IlscoCCL-6-38Ilsco
Technical data 227