for 525…690 V
L1, L2, L3,
T1/U, T2/V,
T3/W
R-, R+/
UDC+,
UDC-
)
lbf·ft lbf·ft lbf·ft
R6 22.1 14.8 7.2
R7 29.5 (22.1 *) 14.8 7.2
R8 29.5 29.5 7.2
R9 51.6 51.6 7.2
Connecting the control cables
See section Control units of the drive (page 141) for the default I/O connections of the
Factory macro of ACS880 primary control program. For other macros and control
programs, see the firmware manual.
■ Connection procedure for frames R1 to R3
1. Fasten the cable conduits to the cable lead-through plate holes. Slide the cables
through the connectors.
2. Strip the cable ends and cut to suitable length (note the extra length of the grounding
conductors).
3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in
the cable entry box.
Electrical installation – North America 131