Derating
■ Surrounding air temperature derating
IP21 (UL Type 1) drives and IP55 (UL Type 12) frames R1…R7
In the temperature range +40…55 °C (+104…131 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F).
To calculate the output current, multiply the current in the ratings table by the derating
factor (k):
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
+55 °C
+131 °F
0.80
-15 °C
+5°F
…
0.85
0.95
IP55 (UL Type 12) frames R8 and R9
Derated output current (I
2
)ACS880-
01-…
Frame55 °C
(131 °F)
50 °C
(122 °F)
45 °C
(113 °F)
40 °C
(104 °F)
35 °C
(95 °F)
U
n
= 230 V
R8192226260274274274A-2
U
n
= 400 V
R8209221234246246246A-3
R8209242278293293293A-3
R9209299345363363363A-3
R9209299345363430430A-3
U
n
= 500 V
R8186216228240240240A-5
R8186216247260260260A-5
R9209298343361361361A-5
R9209298343361414414A-5
U
n
= 690 V