Note:
1. Drive must be mounted in an enclosure of the same or greater volume than the
enclosure minimum volume listed in the table.
2. For R1 frame 480 V drives, enclosures must have a solid bottom directly below the
drive. Fans, filters or louvers cannot be mounted directly below the drive but can be
mounted in adjacent areas on the bottom of the enclosure.
3. When multiple drives are installed in the same enclosure, minimum volume of the
enclosure is determined by the largest enclosure minimum volume of the drives
plus the volume(s) of each additional drive. Example: For 480 V R6 and R3 drive
enclosure, select an enclosure with volume ≥ 53703 in3 + 737 in3 = 54440 in3.
4. UL Open Type, UL Type 1 and UL Type 12 drives can be used inside of the
enclosure. Use drive volume for all three types listed in the table when installing
multiple drives in the panel.
5. ABB circuit breaker part number listed in table is a base part number. Last eight
characters of the breaker "FF000XXX" represent optional accessories which can
be added to the breaker. These accessories have no impact on the performance
or rating of the breakers.
6. When installing a drive, always follow installation instructions and NEC requirements
7. Alternative circuit breakers can be used if they meet certain characteristics. For
acceptable circuit breakers, see the manual supplement (3AXD50000645015
[English]).
Dimensions, weights and free space requirements
IP21Frame
WeightDWH2H1
kgmmmmmmmm
7.0226155370409R1
8.4249155370409R2
10.8261172420475R3
18.6274203490580R4
22.8274203596732R5
42.2357252569727R6
53.0365284621880R7
68.0386300700965R8
95.0413380700955R9
Technical data 217