gG fuses (one fuse per phase)
FuseInput
current
Min. short-
circuit cur-
rent
1)
ACS880-01-…
DIN sizeABB typeVA
2
sAAA
3OFAF3H630500280000063041410200414A-5
U
n
= 690 V
000OFAA000GG166901200167.411507A4-7
000OFAA000GG206902400209.914509A9-7
000OFAA000GG2569040002514.319014A3-7
000OFAA000GG35690120003519280019A-7
000OFAA000GG50690240005023450023A-7
000OFAA000GG50690240005027450027A-7
000OFAA000GG63690300006335520035A-7
0OFAA0GG80690510008042800042A-7
0OFAA0GG80690510008049800049A-7
0OFAA0GG10069095000100611050061A-7
1OFAA1GG160690240000160841700084A-7
1OFAA1GG160690240000160981700098A-7
1OFAA1GG2006903500002001192200119A-7
1OFAA1GG2506907000002501423200142A-7
2OFAA2GG3156908500003151745500174A-7
3OFAA3GG40069013000004002107000210A-7
3OFAA3GG40069013000004002717000271A-7
1)
minimum short-circuit current of the installation
■ Quick guide for selecting between gG and aR fuses
The combinations (cable size, cable length, transformer size and fuse type) in this table
fulfill the minimum requirements for the proper operation of the fuse. Use this table to
206 Technical data