65 kA when protected by fuses given in the fuse tablesRated conditional short-
circuit current Icc (IEC
61439-1)
US and Canada: The drive is suitable for use on a circuit capable of de-
livering not more than 100 kA symmetrical amperes rms at 600 V maxim-
um when protected by fuses given in the fuse table.
Short-circuit current
protection rating (UL
61800-5-1, CSA C22.2
No.274-17) Drive
Frames R1-R8
Short-circuit current
protection rating (UL
508C, CSA C22.2
No.274-17) Drive
Frame R9
US and Canada: The drive is suitable for use on a circuit capable of de-
livering not more than 65 kA symmetrical amperes rms at 480 V maximum
when protected by circuit breakers given in the circuit breaker table.
Short-circuit current
protection rating (UL
61800-5-1, CSA C22.2
No.274-17) Drive
Frames R1-R8
50/60 Hz, variation ± 5%, maximum rate of change 17%/s
Frequency (f
1
)
Max. ± 3% of nominal phase to phase input voltageImbalance
0.98 (at nominal load)Fundamental power
factor (cos phi
1
)
Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous
motors, AC induction servomotors and ABB synchronous reluctance
motors (SynRM motors)
Motor types
0 to U
1
, 3-phase symmetrical. This is indicated in the type designation
label as typical output voltage level as 3 0…U
1
, U
max
at the field weak-
ening point.
Voltage (U
2
)
0…500 HzFrequency (f
2
)
For drives with du/dt filter: 120 Hz
For drives with sine filter: 120 Hz
See section Ratings.
Current
232 Technical data