Mounting orientations
The drive must be installed in an upright position with the cooling section against a wall.
IP21 and IP55 frames R1 to R9 can be mounted side by side.
UL Type 1 frames R1 to R9 can be mounted side by side.
UL Type 12 frames R1 to R3 can be mounted side by side.
UL Type 12 frames R4 to R9 need 100 mm (4 in) between the hoods.
Note: Mounting the drives right next to each other side to side can make it difficult to
read the serial number and rating information on the type designation label.
Required free space
200mm (7.87in)
300 mm (11.81 in)
Examining the installation site
Make sure that the installation site agrees with these requirements:
The installation site has sufficient ventilation to remove heat from the drive. See section
Losses, cooling data and noise (page 220).
The operation conditions of the drive agree with the specifications in section Ambient
conditions (page 233).
The wall is vertical, not flammable and strong enough to hold the weight of the drive.
The material below the installation is not flammable.
42 Mechanical installation