For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-01-xxxx-5
frames R1 to R3 and for types ACS880-01-07A3-7, ACS880-01-09A8-
7, ACS880-01-14A2-7 and ACS880-01-018A-7: 150 m (492 ft).
Maximum recommen-
ded motor cable
length
For ACS880-01-xxxx-2, ACS880-01-xxxx-3 and ACS880-01-xxxx-5
frames R4 to R9 and for types from ACS880-01-022A-7 to ACS880-01-
271A-7: 300 m (984 ft).
Note 1: With motor cables longer than 150 m (492 ft) or switching fre-
quencies higher than default, the EMC Directive requirements may not
be fulfilled.
Note 2: Longer motor cables cause a motor voltage decrease which
limits the available motor power. The decrease depends on the motor
cable length and characteristics. Contact ABB for more information. Note
that a sine filter (optional) at the drive output also causes a voltage de-
crease.
Efficiency
Approximately 98% at nominal power level.
Protection classes
IP21, IP55. Option +P940 and +P944: IP20Degree of protection
(IEC/EN 60529)
UL Type 1, UL Type 12. Option +P940: UL Open Type. For indoor use
only.
Enclosure type (UL
50/50E)
IIIOvervoltage category
(IEC 60664-1)
IProtective class
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
TransportationStorageOperation
in the protective pack-
age
in the protective pack-
age
installed for stationary
use
--0 to 4000 m (13123 ft)
above sea level
1)
Installation site alti-
tude
Above 1000 m (3281 ft)
2)
: see section Derat-
ing (page 184).
-40 to +70 °C (-40 to
+158 °F)
-40 to +70 °C (-40 to
+158 °F)
-15 to +55 °C (5 to
131 °F). No frost al-
lowed. See section De-
rating (page 184).
Air temperature
Technical data 233