Grounding system compatibility check
The standard drive can be installed to a symmetrically grounded TN-S system. If you
install the drive to another system, you may need to disconnect the EMC filter and
ground-to-phase varistor. See ACS880 frames R1 to R11 EMC filter and ground-to-phase
varistor disconnecting instructions (3AUA0000125152 [English]).
WARNING! Do not install the drive with EMC filter options +E200 or +E202
connected to a system that the filter is not suitable for. This can cause danger, or
damage the drive.
WARNING! Do not install the drive with the ground-to-phase varistor connected
to a system that the varistor is not suitable for. If you do, the varistor circuit can
be damaged.
Corner-grounded and midpoint-grounded 525…690 V delta systems
WARNING!
Do not install the drive on a 525…690 V corner-grounded or midpoint-grounded
delta system. Disconnecting the EMC filter and ground-to-phase varistor does
not prevent damage to the drive.
Connecting the power cables
Connection diagram with conduits
This diagram shows power cable connections when conduits are used. For connections
with shielded cables, see chapter Electrical installation IEC (page 89).
118 Electrical installation North America