■ Deratings for special settings in the drive control program
Enabling special settings in the drive control program can require output current derating.
Ex motor, sine filter, low noise
Deratings are needed in these cases:
•
drive is used with an ABB motor for explosive atmospheres (Ex) and EX motor in
parameter 95.15 Special HW settings is enabled
•
sine filter given in the selection table in chapter Filters is used and ABB Sine filter
in parameter 95.15 Special HW settings is enabled
•
Low noise optimization is selected in parameter 97.09 Switching freq mode.
Note: If Ex motors are used together with sine filters, EX motor in parameter 95.15
Special HW settings is disabled and ABB Sine filter in parameter 95.15 Special HW
settings is enabled. Obey the instructions of the motor manufacturer.
Output ratingsACS880-
01-…
ABB Sine filterEX motor (ABB Ex motors)
Heavy-
duty use
Light-
duty
use
Nominal useHeavy-
duty use
Light-
duty
use
Nominal use
I
Hd
I
Ld
P
N
I
N
I
Hd
I
Ld
P
N
I
N
AAkWAAAkWA
U
n
= 230 V
3.54.10.554.33.74.40.754.604A6-2
4.35.90.86.24.66.31.16.606A6-2
6.27.01.57.46.67.11.57.507A5-2
7.49.52.210.07.510.12.210.610A6-2
10.015.14.015.910.616.04.016.816A8-2
15.921.95.523.116.823.15.524.324A3-2
23.129.07.530.524.329.37.531031A-2
314111.043.0384411.046046A-2
4155155845581561061A-2
5562156561711975075A-2
627318.57772832287087A-2
7395221008710122106115A-2
951203012610512730134145A-2
1201453715313415337161170A-2
1451774518616118545195206A-2
1692215523319523855251274A-2
U
n
= 400 V
1.72.20.752.31.802.30.752.402A4-3
Technical data 187