314 Technical data
Definitions
1980A-5 2×D8T + 3×R8i 1980 2574 1819 1400 1715 1901 1300 1481 1000
0990A-5+A004 2×D7T + 2×R8i 990 1287 909 710 857 950 630 741 500
1320A-5+A004 2×D8T + 2×R8i 1320 1716 1212 900 1143 1267 900 987 710
1450A-5+A004 2×D8T + 2×R8i 1450 1890 1332 1000 1256 1392 900 1085 710
1580A-5+A004 2×D8T + 2×R8i 1580 2060 1451 1100 1368 1517 1000 1182 800
1800A-5+A004 2×D8T + 3×R8i 1800 2340 1653 1250 1559 1728 1200 1346 900
1980A-5+A004 2×D8T + 3×R8i 1980 2574 1819 1400 1715 1901 1300 1481 1000
U
N
= 690 V (Range 525…690 V)
0800A-7 1×D8T + 2×R8i 800 1200 735 800 956 768 710 598 560
0900A-7 1×D8T + 2×R8i 900 1350 827 900 1076 864 800 673 630
1160A-7 2×D8T + 2×R8i 1160 1740 1066 1100 1386 1114 1100 868 800
1450A-7 2×D8T + 3×R8i 1450 2175 1332 1400 1733 1392 1250 1085 1000
1650A-7 2×D8T + 3×R8i 1650 2475 1516 1600 1972 1584 1500 1234 1200
2300A-7 3×D8T + 4×R8i 2300 3450 2113 2200 2749 2208 2000 1720 1600
0800A-7+A004 2×D7T + 2×R8i 800 1200 735 800 956 768 710 598 560
0950A-7+A004 2×D8T + 2×R8i 950 1425 873 900 1135 912 800 711 630
1160A-7+A004 2×D8T + 2×R8i 1160 1740 1066 1100 1386 1114 1100 868 800
1450A-7+A004 2×D8T + 3×R8i 1450 2175 1332 1400 1733 1392 1250 1085 1000
1650A-7+A004 2×D8T + 3×R8i 1650 2475 1516 1600 1972 1584 1500 1234 1200
2300A-7+A004 4×D8T + 4×R8i 2300 3450 2113 2200 2749 2208 2000 1720 1600
3AXD00000601909
Nominal ratings
U
N
supply voltage range (see also section Electrical power network specification on page 329)
I
N
nominal output current (available continuously with no over-loading)
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by module
temperature.
I
1
nominal rms input current
P
N
nominal output power
S
N
apparent power in no-overload use
Light-overload use (10% overload capability) ratings
I
Ld
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
P
Ld
output power in light-overload use
Heavy-duty use (50% overload capability) ratings
I
Hd
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
P
Hd
output power in heavy-duty use
Note: The ratings apply to units without option +C132 (marine type approval). For ratings of units with option
+C132, see ACS880 +C132 marine type-approved drive modules and module packages supplement
(3AXD50000037752 [English]).
ACS880-04-… Frame
No-overload use Light-
overload use
Heavy-duty
use
I
N
I
max
I
1
P
N
S
N
I
Ld
P
Ld
I
Hd
P
Hd
A (AC) A (AC) A (AC) kW kVA A kW A kW