164 Technical data
Definitions
U
N
= 500 V
0260A-5 R11 212 260 480 160 225 247 160 240 132
0361A-5 R11 321 361 520 200 313 343 200 260 160
0414A-5 R11 355 414 722 250 359 393 250 361 200
0460A-5 R11 421 460 828 315 398 450 315 414 250
0503A-5 R11 455 503 920 355 436 492 355 460 315
U
N
= 690 V
0174A-7 R11 171 174 284 160 208 165 160 142 132
0210A-7 R11 186 210 348 200 251 200 200 174 160
0271A-7 R11 267 271 420 250 324 257 250 210 200
0330A-7 R11 293 330 542 315 394 320 315 271 250
0370A-7 R11 330 370 660 355 442 360 355 330 315
0430A-7 R11 380 430 740 400 514 420 400 370 355
3AXD10000425795
I
1
Nominal rms input current at 40 °C (104 °F)
I
2
Continuous rms output current. No overload capability at 40 °C (104 °F)
I
max
Maximum output current. Available for 10 seconds at start, then as long as allowed by drive
temperature.
P
N
Typical motor power in no-overload use
S
N
Apparent power in no-overload use
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes.
1)
No overload
P
Ld
Typical motor power in light-overload use
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes.
P
Hd
Typical motor power in heavy-duty use
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F).
Note 2: To achieve the rated motor power given in the table, the rated current of the drive must be higher
than or equal to the rated motor current.
The DriveSize dimensioning tool available from ABB is recommended for selecting the drive, motor and gear
combination.
Drive type
ACS880-17-
Frame
size
Input
current
Nominal ratings
Output ratings
Light-overload
use
Heavy-duty use
I
1
I
2
I
max
P
N
S
N
I
Ld
P
Ld
I
Hd
P
Hd
AAAkWkVAAkWAkW