76 Guidelines for planning the electrical installation
This table shows the minimum cross-sectional area related to the phase conductor size
according to IEC 61800-5-1 when the phase conductor and the protective conductor are
made of the same metal. If this is not so, the cross-sectional area of the protective earthing
conductor shall be determined in a manner which produces a conductance equivalent to
that which results from the application of this table.
Typical cable sizes
The table below gives copper and aluminum cable types with concentric copper shield for
nominal current. For drawings of the terminals, see chapter Dimensions (page 183).
1. The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1
and IEC 60364-5-52/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
2. The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
earth (directly buried). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
Cross-sectional area of the phase conductors
S (mm
2
)
Minimum cross-sectional area of the
corresponding protective conductor
S
p
(mm
2
)
S <
16 S
16 < S <
35 16
35 < S S/2
Drive type
ACS880-17-
Frame
size
IEC
1)
US
2)
Cu cable size Al cable size Cu cable size
mm
2
mm
2
AWG/kcmil
U
N
= 400 V
0293A-3 R11 2 × (3×95) 2 × (3×120) 2 × 3/0
0363A-3 R11 2 × (3×120) 2 × (3×185) 2 × 4/0
0442A-3 R11 2 × (3×150) 3 × (3×120) 2 × 250
0505A-3 R11 3 × (3×95) 3 × (3×150) 2×500 MCM or 3×250 MCM
0585A-3 R11 3 × (3×120) 3 × (3×185) 2×600 MCM or 3×300 MCM
0650A-3 R11 3 × (3×150) 3 × (3×240) 2×700 MCM or 3×350 MCM
U
N
= 500 V
0260A-5 R11 2 × (3×70) 2 × (3×95) 2 × 2/0
0361A-5 R11 2 × (3×120) 2 × (3×185) 2 × 250 MCM
0414A-5 R11 2 × (3×150) 2 × (3×240) 2 × 250 MCM
0460A-5 R11 2 × (3×185) 3 × (3×120) 2×400 MCM or 3×4/0
0503A-5 R11 3 × (3×95) 3 × (3×150) 2×500 MCM or 3×250 MCM
U
N
= 690 V
0174A-7 R11 3×120 2 × (3×70) 4/0
0210A-7 R11 3×185 2 × (3×95) 300 MCM
0271A-7 R11 3×240 2 × (3×120) 400 MCM
0330A-7 R11 2 × (3×95) 2 × (3×150) 2 × 250 MCM or 3×2/0
0370A-7 R11 2 × (3×120) 2 × (3×150) 2 × 300 MCM or 3×3/0
0430A-7 R11 2 × (3×185) 3 × (3×120) 2 × 350 MCM or 3×4/0
3AXD10000425795