Technical data 171
Sine output filter data
Sine output filters are available as option +E206. The table below shows the types and
technical data of the filters and filter cubicles used in the drive.
* Natural convection
Terminal and exit data for the power cables
The locations and sizes of exits are shown in the dimension drawings delivered with the
drive, and in the dimension drawing examples starting on page 183.
The location and size of power cable terminals are shown in the drawings starting on page
193.
IEC
Drive type
ACS880-17-
Sine filter(s) used
I
n/sf mode
Cooling data
Qty Type
Heat dissipation Air flow
AkWm
3
/h (ft
3
/min)
U
N
= 400 V
0293A-3 1 B84143V0390R229 249 1.57 *
0363A-3 1 B84143V0390R229 297 1.57 *
0442A-3 1 B84143V0390R229 390 1.7 *
0505A-3 1 NSIN0900-6 470 3.0 2000 (1177)
0585A-3 1 NSIN0900-6 540 3.4 2000 (1177)
0650A-3 1 NSIN0900-6 600 3.8 2000 (1177)
U
N
= 500 V
0260A-5 1 B84143V0230R229 221 0.9 *
0361A-5 1 B84143V0390R229 289 1.57 *
0414A-5 1 B84143V0390R229 332 1.57 *
0460A-5 1 NSIN0900-6 430 3.3 2000 (1177)
0503A-5 1 NSIN0900-6 470 3.6 2000 (1177)
U
N
= 690 V
0174A-7 1 B84143V0207R230 138 0.93 *
0210A-7 1 B84143V0207R230 161 0.93 *
0271A-7 1 B84143V0207R230 208 0.93 *
0330A-7 1 NSIN0485-6 330 2.2 700 (412)
0370A-7 1 NSIN0485-6 340 2.3 700 (412)
0430A-7 1 NSIN0485-6 360 2.4 700 (412)
Frame
size
Number of holes
in the entry plate
for the power
cables. Hole
diameter 60 mm.
Terminals L1, L2, L3, U2, V2, W2, UDC+/R+,
UDC- and R-
Grounding terminals
Max. phase
conductor
size
Bolt size Tightening
torque
Bolt size Tightening
torque
mm
2
N·m
R11 12 3×240 or
4×185
M12 50...75 N·m M12 50...75 N·m

Table of Contents