Mechanical installation 63
Fastening the cabinet to the floor and wall or roof
General rules
The drive must be installed in an upright vertical position.
The cabinet can be installed with its back against a wall (a), or back-to-back with
another unit (b).
Leave 400 mm (15.75”) of free space above the basic roof level of the cabinet for
cooling.
Leave some space (w) at the side where the cabinet outmost hinges are to allow the
doors to open sufficiently. The doors must open 120° to allow drive and LCL filter
module replacement.
Note 1: Any height adjustment must be done before fastening the units or shipping splits
together. Height adjustment can be done by using metal shims between the cabinet
bottom and floor.
Note 2: If the lifting eyes are removed, refasten the bolts with the sealing rings delivered
with the drive to retain the degree of protection of the cabinet. Drive cabinets with lifting
bars: Remove the lifting bars. Refasten the bolts with the sealing rings delivered with the
drive to retain the degree of protection of the cabinet. Tighten the bolt to a torque of
70 N·m (52 lb·ft).
a
b
120°
w
> 400 mm (15.75”)