EasyManua.ls Logo

ABB ACS880-17 - Marine Construction (Option +C121)

ABB ACS880-17
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 Operation principle and hardware description
Marine construction (option +C121)
The option includes the following accessories and features:
reinforced mechanics
grab railings
door flush bolt which allows the door to open 90 degrees and prevents it from
slamming close
self-extinctive materials
flat bars at base of the cabinet for fastening
fastening braces at the top of the cabinet.
Required options: Appropriate additional wire marking option (see page 45) according to
the requirements of the classification society
Related options: halogen-free materials and wiring (+G330)
UL listed (option +C129)
The option includes factory inspection of the cabinet according to UL 508C and the
following accessories and features:
US type main switch and fuses
top entry and exit of cables
US cable conduit entry (plain plate without ready-made holes)
all components UL Listed/Recognized
maximum supply voltage 600 V.
Related options: +H350 (bottom entry of cables), +H352 (bottom exit of cables) and
+H358 (cable conduit entry)
The option is not available with +C121 (marine construction) or +E206 (sine output filter).
CSA approved (option +C134)
The option includes the following accessories and features:
US/CSA type main switch fuse
bottom entry and exit of cables
US cable conduit entry (plain plate without ready-made holes)
all components UL/CSA listed/recognized
maximum supply voltage 600 V.
The option is not available with +C121 (marine construction) or +E206 (sine output filter).
Plinth height (options +C164 and +C179)
The standard height of the cabinet plinth is 50 mm. These options specify a plinth height of
100 mm (+C164) or 200 mm (+C179).
Seismic design (option +C180)
This option involves seismic capability according to International building code 2012, test
procedure ICC-ES AC-156. The installation level must not exceed 25% of the height of the
building, and SDS (installation site specific spectral acceleration response) must not
exceed 2.0 g.