Operation principle and hardware description 47
The output indication of the relay can be wired by the customer for example to
the main contactor or breaker control circuit of the drive, to open it in case of motor
overtemperature,
the appropriate digital input of the drive, to trip the drive and generate a fault message
in case of motor overtemperature, or
an external monitoring circuit.
Option +L513 is an ATEX-certified thermal protection function that has the same external
connectivity as +L505. In addition, +L513 comes with +Q971 (ATEX-certified safe
disconnection function) and is wired at the factory to activate the Safe torque off function of
the drive in an overtemperature situation. A manual reset for the protection function is
required by Ex/ATEX regulations. For more information, see ATEX-certified motor thermal
protection functions for cabinet-built ACS880 drives (options +L513+Q971 and
+L514+Q971) user’s manual (3AXD50000014979 [English]).
Options +2L505 and +2L513 duplicate options +L505 and +L513 respectively, containing
the relays and connections for two separate measurement circuits.
+L536, +L537
An alternative to a thermistor relay option is the FPTC-01 (option +L536) or FPTC-02
(option +L537, also requires option +Q971) thermistor protection module. The module
mounts onto the drive control unit, and has reinforced insulation to keep the control unit
PELV-compatible. The connectivity of the FPTC-01 and the FPTC-02 is the same.
FPTC-02 is an ATEX-certified thermistor protection module, Type Examined as a
protective device within the scope of the European ATEX Product Directive.
For protection purposes, the FPTC has a “fault” input for the PTC sensor. An
overtemperature situation executes the SIL/PL-capable SMT (Safe motor temperature)
safety function by activating the Safe torque off function of the drive.
The FPTC also has a “warning” input for the sensor. When the module detects
overtemperature through this input, it sends a warning indication to the drive.
For more information and wiring examples, see the module manuals and the circuit
diagrams delivered with the drive.
More information
See
firmware manual for parameter settings
ATEX-certified motor thermal protection functions for cabinet-built ACS880 drives
(options +L513+Q971 and +L514+Q971) user’s manual (3AXD50000014979
[English])
FPTC-01 thermistor protection module (option +L536) for ACS880 drives users
manual (3AXD50000027750 [English])
FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option +L537
+Q971) for ACS880 drives user’s manual (3AXD50000027782 [English])
Wiring the PTC thermistor relay(s) (options +L505, +2L505, +L513, +2L513) on page
100
circuit diagrams delivered with the drive for the actual wiring.

Table of Contents

Other manuals for ABB ACS880-17

Related product manuals