EasyManua.ls Logo

ABB ACS880-17 - Technical Data

ABB ACS880-17
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control unit of frame R11 119
Technical data
Power supply
(XPOW)
24 V (±10%) DC, 2 A
Supplied from the power unit of the drive, or from an external power supply
through connector XPOW. Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG).
Relay outputs RO1…RO3
(XRO1 XRO3)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
250 V AC / 30 V DC, 2 A
Protected by varistors
+24 V output
(XD24:2 and XD24:4)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
Total load capacity of these outputs is 4.8 W (200 mA / 24 V) minus the
power taken by DIO1 and DIO2.
Digital inputs DI1…DI6
(XDI:1 XDI:6)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP (DI1…DI5), NPN (DI6)
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
DI6 (XDI:6) can alternatively be used as an input for PTC sensors.
“0” > 4 kohm, “1” < 1.5 kohm
I
max
: 15 mA (for DI6 5 mA)
Start interlock input DIIL
(XD24:1)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Input type: NPN/PNP
Hardware filtering: 0.04 ms, digital filtering up to 8 ms
Digital inputs/outputs DIO1
and DIO2
(XDIO:1 and XDIO:2)
Input/output mode selection
by parameters.
DIO1 can be configured as a
frequency input (0…16 kHz
with hardware filtering of 4
microseconds) for 24 V level
square wave signal
(sinusoidal or other wave form
cannot be used). DIO2 can be
configured as a 24 V level
square wave frequency
output. See the firmware
manual, parameter group 11.
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
A
s inputs:
24 V logic levels: “0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Filtering: 0.25 ms
As outputs:
Total output current from +24VD is limited to 200 mA.
Reference voltage for
analog inputs +VREF and
-VREF
(XAI:1 and XAI:2)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
10 V ±1% and –10 V ±1%, R
load
1…10 kohm
Analog inputs AI1 and AI2
(XAI:4 XAI:7).
Current/voltage input mode
selection by jumpers. See
page 116.
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
Current input: –20…20 mA, R
in
: 100 ohm
Voltage input: –10…10 V, R
in
: > 200 kohm
Differential inputs, common mode range ±30 V
Sampling interval per channel: 0.25 ms
Hardware filtering: 0.25 ms, adjustable digital filtering up to 8 ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
Inaccuracy for Pt100 sensors: 10 °C (50 °F)
R
L
DIOx
DIOGND
+24VD

Table of Contents