96 Electrical installation
Routing the control cables inside R11 cabinet
1. Stop the drive and do the steps in section Electrical safety precautions (page 16)
before you start the work.
1. Open the cabinet door.
2. If there is a mounting plate/two plates
above the fan, loosen the four screws of the
plate and pull out the plate/s. Unplug the connectors and remove the plate/s.
If there is no mounting plate/s
, but instead a shroud/s above the fan, undo the four
screws and remove the shroud/s.
3. Remove the “door” fan (see section Replacing the cabinet “door” fan on page 136).
4. The connection terminals are at the left-hand side of the cabinet.
See also page 38.