202 The Safe torque off function
Single drive (internal power supply)
Dual-channel connection
Single-channel connection
+24 V
OUT1
SGND
IN2
T1/U, T2/V, T3/W
Control logic
UDC+
UDC–
A
K
IN1
ACS880-17
Motor-side converter
control unit
+24 V
OUT1
SGND
IN2
K
IN1
Notes:
Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL
classification is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.