Technical data 167
High speed mode
Selection High speed mode of parameter 95.15 Special HW settings improves control
performance at high output frequencies. ABB recommends it to be selected with output
frequency of 120 Hz and above. Contact ABB for the derating.
Fuses (IEC)
The drive is equipped with aR fuses listed below as standard.
Note 1: See also Implementing thermal overload and short-circuit protection on page 80.
Note 2: Fuses with higher current rating than the recommended ones must not be used. Fuses with lower
current rating can be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the fuse
does not exceed the melting curve of the fuse mentioned in the table.
Drive type
ACS880-17-
Input
current
(A)
Ultrarapid (aR) fuses (one fuse per phase)
A
A
2
s
V Manufacturer Type Size
U
N
= 400 V
0293A-3 257 500 145000 690 Bussmann 170M5410 2
0363A-3 321 630 210000 690 Bussmann 170M6410 3
0442A-3 401 700 300000 690 Bussmann 170M6411 3
0505A-3 401 800 465000 690 Bussmann 170M6412 3
0585A-3 505 900 670000 690 Bussmann 170M6413 3
0650A-3 569 1000 945000 690 Bussmann 170M6414 3
U
N
= 500 V
0260A-5 212 400 74000 690 Bussmann 170M5408 2
0361A-5 321 630 210000 690 Bussmann 170M6410 3
0414A-5 355 700 300000 690 Bussmann 170M6411 3
0460A-5 421 700 300000 690 Bussmann 170M6411 3
0503A-5 455 800 465000 690 Bussmann 170M6412 3
U
N
= 690 V
0174A-7 171 400 74000 690 Bussmann 170M5408 2
0210A-7 186 400 74000 690 Bussmann 170M5408 2
0271A-7 267 500 105000 690 Bussmann 170M5410 2
0330A-7 293 630 210000 690 Bussmann 170M6410 3
0370A-7 330 630 210000 690 Bussmann 170M6410 3
0430A-7 380 700 300000 690 Bussmann 170M6411 3
3AXD10000425795