206 The Safe torque off function
Use
1. Open the activation switch, or activate the safety functionality that is wired to the STO
connection.
2. STO inputs on the motor-side converter control unit de-energize, and the drive control
unit cuts off the control voltage from the drive IGBTs.
3. The control program generates an indication as defined by parameter 31.22 (refer to
the firmware manual of the drive).
4. The motor coasts to a stop (if running). The drive will not restart while the activation
switch or safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or reseting the safety functionality
that is wired to the STO connection.
6. Reset any faults before restarting.
Test the operation of the STO function when the motor is stopped.
Give a stop command to the drive (if running) and wait until the motor shaft is at a standstill.
Ensure that the drive operates as follows:
Open the STO circuit. The drive generates an indication if one is defined for ‘stopped state in
parameter 31.22 (see the firmware manual).
Give a start command to verify that the STO function blocks the drive’s operation. The motor
should not start.
Close the STO circuit.
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the STO function when the motor is running.
Start the drive and ensure the motor is running.
Open the STO circuit. The motor should stop. The drive generates an indication if one is defined for
‘running’ state in parameter 31.22 (see the firmware manual).
Reset any active faults and try to start the drive.
Ensure that the motor stays at a standstill and the drive operates as described above in testing the
operation when the motor is stopped.
Close the STO circuit.
Reset any active faults. Restart the drive and check that the motor runs normally.
Test the operation of the failure detection of the drive. The motor can be stopped or running.
Open the 1st channel of the STO circuit (wire coming to IN1). If the motor was running, it should
coast to a stop. The drive generates a FA81 Safe Torque Off 1 loss fault indication (see the
firmware manual).
Give a start command to verify that the STO function blocks the drive’s operation. The motor
should not start.
Close the STO circuit.
Reset any active faults. Restart the drive and check that the motor runs normally.
Open the 2nd channel of the STO circuit (wire coming to IN2). If the motor was running, it should
coast to a stop. The drive generates a FA82 Safe Torque Off 2 loss fault indication (see the
firmware manual).
Give a start command to verify that the STO function blocks the drive’s operation. The motor
should not start.
Close the STO circuit.
Reset any active faults. Restart the drive and check that the motor runs normally.
Document and sign the acceptance test report which verifies that the safety function is safe and
accepted for operation.