ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/8,
1
/4 and
1
/2 DIN 10 Specification
112 IM/CM/S–EN Rev. R
RTD Maximum Range
°C (°F)
Accuracy
(% of reading)
Pt100
–200 to 600
(–325 to 1100)
0.1 % or ±0.5 °C
(0.9 °F)
Linear Inputs
Standard
Analog Input
Accuracy
(% of reading)
Millivolts
Milliamps
Volts
Resistance
(low)
Resistance
(high)
0 to 150 mV
0 to 45 mA (CM10 and CM30)
0 to 50 mA (CM50)
0 to 25 V
0 to 550
0 to 10 k
0.1 % or ±20 µV
0.2 % or ±4 µA
0.2 % or ±20 mV
0.2 % or ±0.1
0.5 % or ±10
Sample Interval
125 ms per sample
Digital Inputs
Type Volt-free or 24 V
Minimum pulse
duration
Analog inputs 1 and 2:
Single input configured – 250 ms
Both inputs configured as analog or
digital – 500 ms
Analog inputs 3 and 4 (not CM10):
Single inputs configured – 250 ms
Both inputs configured as analog or
digital – 500 ms
Consider analog inputs 1 / 2 and 3 / 4
independently
Frequency input*
Frequency range
1-signal
0-signal
0 to 6000 Hz
15 to 30 V
–3 to 5 V
*For use with devices with open collector outputs