ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/8,
1
/4 and
1
/2 DIN 10 Specification
IM/CM/S–EN Rev. R 113
Outputs
Controls / retransmission outputs
Relays
Digital input / output
2-Wire transmitter power supply
Number 2 (1 standard, 1 optional)
Type Configurable as analog or digital pulse
Isolation Galvanically isolated from the rest of the circuitry,
500 V for 1 minute
Analog range 0 to 20 mA programmable
Load 750 Max.
Accuracy 0.25 % of output or ± 10µA
Number CM10 / CM30: 4 (1 standard, 3 optional)
CM50: 4 (2 standard, 2 optional)
Type CM10, CM30: Standard with changeover
contacts. Optional contacts selectable as N/O
or N/C (by jumper)
CM50: Selectable as N/O or N/C (by jumper)
Contact ratings
CM10:
CM30, CM50:
Relay 1: 5 A, 240 V
Relays 2, 3, 4: 5 A, 240 V (max. ambient
40 °C (104 °F)
Relays 2, 3, 4: 2 A, 240 V (max. ambient
55 °C (131 °F)
5 A, 240 V
Update rate 125 ms
CM10 2 (optional)
CM30 / CM50 6 (2 standard, 4 optional)
Type User-programmable as input or output
Minimum input pulse duration – 125 ms
Input
– volt-free or 24 V DC
– 1-signal: 15 to 30 V
– 0-signal: –3 to 5 V
– Conforms to IEC 61131-2
Output
– Open collector output
– 30 V, 100 mA max. switched
– Conforms to IEC 61131-2
Update rate 125 ms
CM10 1 (standard)
CM30 / CM50 2 (1 standard, 1 optional)
Voltage 24 V DC
Drive 2 loops 45 mA max.