Error messages
144 FEX300, FEX500 OI/FEX300/FEX500-EN
Error no. /
Range
Text on the LCD
display
Current
output
behavior
Digital output
behavior
Pulse
output
behavior
Display Error
maskable?
C190.045
Configuration
An alarm is
simulated
Switch off
alarm simulation
Current value No response Current value Current
value
No
C186.009
Configuration
Tx Simulator/
Calibrator mode
Switch off
Calibrator Mode
Current value Current value Current value Current
value
Mask group
C185.030
Operation
Hold last good
known value
Switch OFF
Noise Reduction
ABB Service
Current value No response Current value Current
value
Mask group
C184.010
Configuration
The Flowrate
is set to zero
Check digital in
terminals 81,82
4 mA (0 % flow) No response 0 Hz 0 % Mask group
C182.008
Configuration
Flowrate
Simulation
Switch off
Simulation Mode
Current Value
or High Alarm
(flow > 105 %)
No response,
Min/Max or General
Alarm
Current value Current
value
Mask group
C178.000
Configuration
Simulated/
Fixed Current Output
Simulation Mode?
HART address>0?
Simulated
value
No response Current value Current
value
Mask group
C177.015
Configuration
HART Address <>0
Multidrop Mode
Set HART
Addr. = 0
4 mA Current value Current value Current
value
Mask group
C176.011
Configuration
Totalizer Stop
Check digital in
terminals 81,82
Current value No response 0 Hz Current
value
Mask group
C175.013
Configuration
Totalizer Reset
Check digital in
terminals 81,82
Current value No response Current value Current
value
Mask group
C174.02
Configuration
Pulse Simulation
selected on DO1
Switch off
Simulation Mode
Current value No response Simulated value Current
value
Mask group
C172.04
Configuration
Pulse Simulation
selected on DO2
Switch off
Simulation Mode
Current value No response Simulated value Current
value
Mask group
C168.01
Configuration
Logic Simulation
selected on DO1
Switch off
Simulation Mode
Current value Simulated value No response Current
value
Mask group
C164.003
Configuration
Logic Simulation
selected on DO2
Switch off
Simulation Mode
Current value Simulated value No response Current
value
Mask group
C158.039
Configuration
Simulation of
HART frequency
Switch off
Simulation Mode
Current value No response Current value Current
value
Mask group