Parameterization
124 FEX300, FEX500 OI/FEX300/FEX500-EN
7.4.9 Menu: Totalizer
Menu / Parameter Value range Description
Totalizer
Reset Vol. Totals
Select the "Reset Vol. Totals" submenu.
Batching
1)
Select the "Batching" submenu.
Edit Vol. Totals
Select the "Edit Vol. Totals" submenu.
Totalizer / Reset Vol. Totals
Totalizer Fwd
Resets forward totalizer to zero.
Totalizer Rev
Resets reverse totalizer to zero.
Totalizer Net
Reset the differential totalizer to zero.
All Vol. Totalizer
Resets all totalizers to zero.
Totalizer / Batching
1)
Damping On / Off Switch on / off the damping.
Default setting: On
Important (Notice)
In order to achieve a shorter response time for
the fill function, the damping must be switched
off.
The fill time should be > 3 seconds.
Preset Batch Tot. -
Set the fill quantity When the defined fill quantity is
reached, the configured digital output is activated.
Lag Corr. Mode Automatic / Manual Select the overrun correction.
Closing the fill valve takes some time. As a result,
some more fluid is added, although the fill quantity is
already reached and the contact for closing the valve
is actuated.
With "Automatic overrun correction" the set fill quantity
is corrected with the overrun quantity.
Lag Corr. Quantity -100.000 ... 100.000 Manual entry of the overrun quantity.
italics = Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.