Commissioning
OI/FEX300/FEX500-EN FEX300, FEX500 57
6.3.1 Example of local address setting (DIP switch 8 = On)
Integral mount design Remote mount design
G01033
12345678
On
1 1
2
2
Fig. 55: Position of DIP switches
1Transmitter plug-in module 2DIP switch
Switches 1, 5, 7 = ON means: 1+16+64 = 81 Bus address 81
Switch 1 2 3 4 5 6 7 8
Status Device address Address mode
Off 0 0 0 0 0 0 0 Bus
On 1 2 4 8 16 32 64 Local
Switch assignments
Switch Assignment
1 … 7 PROFIBUS address
8 Defines the addressing mode:
Off = Set address via bus (factory setting)
On = Set address via DIP switches nos. 1 ... 7 (local)