Electrical connections 
OI/FEX300/FEX500-EN FEX300, FEX500  41 
 
Observe the following points when routing cables: 
•  A magnet coil cable (red and brown) is run parallel to the signal lines (violet and blue). As a 
result, only one cable is required between the sensor and the transmitter. Do not run the 
cable over junction boxes or terminal blocks 
•  The signal cable carries a voltage signal of only a few millivolts and must, therefore, be 
routed over the shortest possible distance. The max. allowable signal cable length is 50 m 
(164 ft) without pre-amplifier and 200 m (656 ft) with pre-amplifier. 
•  Avoid routing the cable in the vicinity of electrical equipment or switching elements that can 
create stray fields, switching pulses, and induction. If this is not possible, run the 
signal/magnet coil cable through a metal pipe and connect this to the station ground. 
•  All leads must be shielded and connected to earth ground. 
•  To shield against magnetic interspersion, the cable contains outer shielding that is attached 
to the SE clamp. 
•  The supplied stranded steel wire is also connected to the SE clamp 
•  Do not damage the sheathing of the cable during installation. 
•  Make sure during installation that the cable 
is provided with a water trap (1). For vertical 
installation, align the cable glands pointing 
downward. 
 Fig. 36