112 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
9 Diagnosis / error messages
Overview of error states and alarms
State / Error
Flow rate
indicator
display
Notification
with simulation
at current
output
Current
output
Pulse output
Switch output
Message with
HART
Collective
alarm
Min Alarm
Max
Alarm
Max/Min
Alarm
Empty
conduit
Ext.
Diag.
Alarm
0 = ‘Empty conduit’
0 %
Prog.Al.
DLR
0 %
Alarm
Alarm
More Stat avai.
1 = ‘AD converter/DSP’
0 %
Prog.Al.
0 %
Alarm
Trans Mal F.
2 = ‘Driver’
0 %
Prog.Al.
0 %
Alarm
Trans Mal F.
3= ‘Flow rate > 103 %’
103 %
Yes
High.Al
103 %
Alarm
PV out Limits
4 = ‘Ext. Zero Return”
0 %
0 %
0 %
Alarm
More Stat avai.
5 = ‘Database’
0 %
Yes
Prog.Al.
0 %
Alarm
Trans Mal F.
6 = ‘Totalizer’
Yes
Alarm
More Stat avai.
A = ‘Max Alarm’
Yes
Alarm
Alarm
Alarm
More Stat avai.
B = Min Alarm’
Yes
Alarm
Alarm
Alarm
More Stat avai.
C = ‘ext. database”
0 %
Yes
Prog.Al.
0 %
Alarm
Trans Mal F.
D = ‘Old sensor’
0 %
Yes
Prog.Al.
0 %
Alarm
Trans Mal F.
E = ‘DC to high’
0 %
Yes
Prog.Al.
0 %
Alarm
Trans Mal F.
F = ‘FRAM in sensor’
0 %
Yes
Prog.Al.
0 %
Alarm
Trans Mal F.
G = ‘Diagnosis error’
Alarm
Alarm
Trans Mal F.