FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E 115
Warning messages during operation
Warning code and ID letter
Before operation with flow, a flowrate can be
simulated. The output values correspond to
the simulated flowrate entered.
After completing the simul
ation
program, switch off the
parameter ‘Simulation Mode’.
All totalizers (forward/reverse, diff. and
overflow counters are reset.)
External totalizer reset was
performed.
Open the switch at the contact
input
(terminal 81, 82).
Only for checking the transmitter using
Simulator 55XC4000.
After running the simulation on
the simulator, switch off the
parameter ‘Test Mode’.
communication, the functional
test for the switch output or switch input was
started, the Warning ‘4’ is displayed.
Leave the routine once the
functional test has completed.
1)
Transmitter has detected additional flowmeter
sensor data and loaded it to the internal FRAM.
System data and sensor data are loaded.
Defective FRAM, repair unit,
replacement unit.
Write down all totalizer values,
totalizers should be reset.
1)
mitter has detected an error in the
internal FRAM and has repaired the data with
content of the external FRAM.
Defective FRAM, repair unit,
replacement unit.
Check the setup data and correct,
if necessary.
1)
Transmitter has detected an error in the
external FRAM and has repaired the data with
content of the internal FRAM.
Defective FRAM or data was
modified.
Check the setup data and correct,
if necessary.
Forward totalizer has reac
hed the maximum
count and has restarted at zero.
-
scaled, 1
overflow as value was totalized.
Reset totalizer, if necessary.
Reverse totalizer has reached the maximum
count and has restarted at zero.
-
scaled, 1
overflow as value was totalized.
Reset totalizer, if necessary.
The difference totalizer has reached the
maximum count and has restarted at zero.
-
value was totalized.
Reset totalizer, if necessary.
1) Warning is displayed for 30 seconds.