116 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
… 9 Diagnosis / error messages
… Warning messages during operation
Warning code and ID letter
If the flow direction is forward, the warning is
displayed in case of reverse flow.
Reverse flow direction, possibly
defective damper or c
heck
Prevent reverse flow or change
flow direction to forward/reverse.
2)
The HART device address was changed to an
address other than zero. The current output
remains frozen at 4 mA.
to 15 selected. The
current output thereby remains
set at 4 mA.
Select 0 as address, if the current
output should be 4
to 20 mA.
2) 3)
Test the current output. Check the value set at
the terminals using a digital voltmeter or the
process instru
mentation.
Enter the functional test of the
current output directly in mA
for simulation.
Exit the functional test of current
output.
2) 3
)
Test the pulse output. Check the configured
pulse at the output with a meter.
Simulation pulse output on.
Exit the functional test for the
pulse output.
2) 3)
Adjustment started for system zero point
adjustment via the contact input for internal
adjustment (for ABB Service only).
is closed
For ABB Service personnel only.
The external contact is open
again.
For ABB Service personnel only.
Warning results only when the ‘Noise
reduction’
function is activated.
Measuring signal affected by
powerful
interference signal.
Reduce interference to lower level
or shut off. Where applicable,
Consult with the factory service
department.
Diagnostic or wiring warning
-Max over/undershoot for
diagnostic values. Wiring error
for
electrode circuit. Coil short-
Retrieve details of warning
message under the Status
submenu in the Diagnosis
warning register. Where
applicable, Adjust limit value.
Retrieve details of warning
message under the Status
submenu in the Wiring
warning
Warning 16 only for Profibus PA and FF devices.
Warning 16 corresponds to Warning
2) Transmitter must be equipped with HART communication protocol.
3) Warning is displayed only if the function is called by an external HART protocol command.