40 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
… 6 Electrical connections
… Terminal assignment
Retrofit for model 10D1422: DN 3 to DN 1000 (¹⁄₁₀ to 40”); model 10DI1425 and 10DS3111A-E:
DN 500 to DN 1000 (20 to 40”)
S4 transmitter (wall mount housing)
Sensor
Functional ground (busbar)
Pulse output
1)
Switch input
1)
Switch output
1)
Current output
1)
Power supply
Low voltage: 100 to 230 V AC, terminals L, N,
Frequency: 47 Hz ≤ f ≤ 53 Hz; 50 Hz power supply
Frequency: 56 Hz ≤ f ≤ 64 Hz; 60 Hz power supply
Shielded signal cable: ABB order no. D173D025U01
or incorporate in existing wiring
Reference cable:
Only for connection to model 10D1422
Close terminals: 6,7 and hook switch S903
Magnetic coil supply:
Magnet coil supply via supply power
Terminal board: D685A1020U03
Figure 37: Sensor standard DN 3 to DN 1000 (1/10 to 40”), transmitter field mount housing
1) See the chapter ‘Connection examples for peripherals’ in the operating instruction and/or on the data sheet
Note
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.