36 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
6 Electrical connections
Terminal assignment
Standard DN 3 to DN 1000 (¹⁄₁₀ to 40”)
S4 transmitter (wall mount housing)
Sensor
1
Functional ground (busbar)
2
Pulse output
1)
3
Switch input
1)
4
Switch output
1)
5
Current output
1)
6
Magnetic coil cable:
shielded 2 x 1 mm2 CE type 227 TEC 74
ABB order no. D173D147U01, 10 m included in shipment, standard
7
Power supply
Low voltage: 100 ... 230 V AC, terminals L, N,
Extra-low voltage: 20.4 ...26.4 V AC;
Extra-low voltage: 20.4 ... 31.2 V DC
Extra-low voltage: Terminals 1+, 2-,
Frequency: 47 Hz ≤ f ≤ 53 Hz; 50 Hz power supply
Frequency: 56 Hz ≤ f ≤ 64 Hz; 60 Hz power supply
8
Steel shielding
9
Aluminum foil
0
Yellow
k
Shield
l
Blue
m
Red
n
White
o
Shielded signal cable:
ABB order no. D173D025U01, 10 m included in delivery
Figure 34: Electrical connection sensor standard DN 10 ... DN 1000 (⅜ ... 40”)
1) See the chapter ‘Connection examples for peripherals’ in the operating instruction and/or on the data sheet
Note
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.