78 FSM4000 ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
… 8 Operation
… Parameter descriptions
Submenu / parameter Value range Remark
Identifier
Curr. Variant Read only
Active pulse without
HART
Active pulse with HART
Passive pulse without
HART
Passive pulse with HART
PROFIBUS PA
FOUNDATION Fieldbus
FF
Variant error
Displays the pulse output and communication configuration for
the shipped model.
User-defined text A TAG number to identify the flowmeter sensor, max. 32-
character limit.
‘-----------------------’
User-defined text A TAG number to identify the transmitter, max. 32-character
limit.
‘-----------------------’
Interface
Communication Without
HART
1. HART communication
Set the HART communication to ON or OFF. When HART
communication is not required, Current Output ranges 0-20, 0-
10, 2-10 mA can be selected. For HART communication, the
current output is always 4 - 20 mA.
No selection available for standard devices (without HART
hardware).
Numerical entry
0 ... 15
For devices with HART protocol, an address between 0 ... 15 can
be selected. If Address 0 is entered, the current output for the
flow rate will also change by 4 - 20 mA. If more devices are
connected to the bus and the address 1 - 15 is selected, the
transmitter will work in multidrop mode. The current output
value then remains frozen at 4 mA. In this case, the output values
can only be read using HART communication. Warning 11 is
displayed.
No entry for standard devices (without HART hardware).
0