Paperless recorder 7 Configuration
OI/RVG200-EN 115
7.10.3 Hybrid modules
Output C1(to D6)
Output Mode Select the output mode required Analog, Digital or TxPSU.
Note. The following parameter is displayed only if Output Mode is set to Analog or Digital.
Source Select the output source required.
An analog output source is the internal analog signal used to generate the
analog output signal.
A digital output source is the internal digital source used to activate /
de-activate a digital output.
Note. If a digital output is used to provide a totalizer count pulse, the
maximum pulse frequency is 1 Hz.
Note. The following parameters are displayed only if Output Mode is set to Analog.
Engineering low
Engineering high
Set the required analog output engineering range.
Note. These settings are the engineering values corresponding to the
Electrical low and Electrical high values below.
Electrical low
Electrical high
Set the required analog output electrical range.
These values are the minimum and maximum values of the current output,
in electrical units range 0 to 23 mA.
Note. The following parameter is displayed only if Output Mode is set to Digital.
Polarity Select the digital output source polarity.
Note. When set to Positive, the digital output is energized when the
digital source is active (On).
Analog output
engineering high
Analog output
engineering low
Analog output
electrical high
Analog output
electrical low
Source range high
Source range low