ScreenMaster RVG200
Paperless recorder 7 Configuration
102 OI/RVG200-EN
7.9.5 Totalizer configuration
Note.
The totalizer tabs are displayed only if the Totalizer option is enabled.
Current totalizer values are displayed in the Indicator view see Section 4.5.2, page 31
(Operation) and Section 7.8.3, page 84 (Configuration), respectively.
For analog sources, the total value of a signal is calculated by counting pulses produced at a rate
proportional to the input. For digital sources, off / on transitions are counted to produce a batch
total.
Totalizer A (B)
Setup
Mode Select the totalizer operation mode:
Off
Standard (9 digits)
Standard (7 digits)
F0
Timer (digital totalizers only).
Direction Note. Displayed only if Mode is set to Standard (9 digits), Standard
(7 digits) or Timer (digital totalizers only).
When Direction is set to Up, the totalizer counts up from the Preset count
value to the Predetermined count value see page 104.
Wrap enable If Wrap enable is set to On, the total is reset automatically to the Preset
count
value once the Predetermined count value is reached.
If Wrap enable is set to Off, the count stops when the Predetermined count
value is reached.
Note. A wrap pulse, with a duration of 2 seconds, occurs if the total
reaches the Predetermined count value and Wrap enable is set to On.IfWrap
enable
is set to Off, the wrap pulse becomes active when the
Predetermined count value is reached and remains active until the totalizer
is reset. The pulse can be assigned to a relay, digital output or digital
counter.