Paperless recorder 7 Configuration
OI/RVG200-EN 127
7.11 Functions
7.11.1 Custom linearizers
Fig. 7.17 Functions configuration
Linearizer
Adjust custom
linearizer 1 (2)
Touch adjacent to the linearizer to be adjusted to open the Adjust
custom linearizer screen.
Touch or use / to select the point to be modified.
Touch to open the digipad to change the position of that point.
Touch to return to the Functions screen.
Each linearizer has 20 breakpoints. Both X and Y values are set as
percentages.
Custom linearizers can be applied to any analog input by selecting them
as the linearizer type for that input see Linearizer Type, page 90.
Note.
X is input to the linearizer expressed as a percentage of the
electrical range.
Y is output expressed as a percentage of the engineering range.