ScreenMaster RVG200
Paperless recorder 7 Configuration
74 OI/RVG200-EN
7.7.5 Security
Note. User 1 is the System Administrator and is able to change the Security type and all other security
parameters. Other users can change only the Logging security setting and only if Security system is set to
Basic.
Security
Security type Set the Security type.
Security system Select Basic or Advanced security – see Section 7.2, page 59.
Configuration security Set the method of access to the Configuration level.
If Password protected is selected, access is via the password set
for the user – see Section 7.7.6, page 76.
If Switch protected is selected, access to the Configuration level is
prohibited for all users once the changes have been saved and
made active. Access to the Configuration level is then achieved
only by setting the internal security switch to the 'Configuration
level not protected' position – see Fig. 7.3, page 62.
Security Options Note. Displayed only if Security system is set to Advanced.
Logging security When set to On, access to the Logging level is protected by each user's
unique password.
Acknowledge security When set to On, each user must enter their unique password in order to
acknowledge alarms.
Logging security Note. Displayed only if Security system is set to Basic.
When set to On, access to the Logging level is protected by a single,
4-digit password for all users.
Logging password Note. Displayed only if Security system is set to Basic and Logging
security is set to On.
Enter the password to be used by all users to access the Logging level.