Paperless recorder 7 Configuration
62 OI/RVG200-EN
Referring to Fig. 7.3, set the internal security switch as follows:
1. Isolate the recorder from the power supply.
2. Remove tamper-evident seal A (if fitted).
3. Unscrew jacking screw B securing the recorder to the case and remove the recorder from its case.
4. Set security switch C to the 'Configuration level not protected' position (toward the front of the
recorder).
5. Refit the recorder to its case and secure with jacking screw B.
6. Refit tamper-evident seal A (if required).
7. Restore the power supply to the recorder.
Note. The internal security switch is used to access the Configuration level when Configuration
security
is set to Internal switch protected. Do Not use the switch to access the Configuration
level when Configuration security is set to Password protected (default setting) unless the password
has been forgotten. The switch overrides password protection, enabling free access to the
Configuration level.
Fig. 7.3 Setting the security switch
A
B
C
Configuration level
protected
Configuration level
not protected