ScreenMaster RVG200
Paperless recorder 7 Configuration
126 OI/RVG200-EN
7.10.10 RS485 (MODBUS) communications
Refer to Appendix B, page 149 for further information on using the MODBUS link.
Note. This Section is applicable only if the optional MODBUS module is fitted.
RS485
Protocol Select the MODBUS protocol required.
MODBUS Slave
MODBUS Master
recorder operates as a MODBUS Slave
recorder operates as a MODBUS Master
Type Set according to the number of transmission wires connected to the
recorder.
4-wire
2-wire
Baud rate Set the Baud rate used by the host system: 1200, 2400, 4800, 9600,
19200, 38400, 115200.
Parity Set the Parity used by the host system: None, Odd, Even.
Address Note. Displayed only if Protocol is set to MODBUS Slave.
Set a unique MODBUS Address (between 1 and 247) to enable the host
system to identify the recorder on a MODBUS link.
Note. Maximum 32 slaves per loop.
Note. The remaining parameters are displayed only if Protocol is set to MODBUS Master.
Poll rate Set the poll rate in milliseconds minimum 0, maximum 3600000.
Poll fail limit Set the number of successive polls permitted to fail before the data is
marked as a failed input minimum 0, maximum 4.
Poll rate interval Set the time interval between individual messages within a poll.
Response Timeout Set the timeout time in milliseconds for a single poll minimum 0,
maximum 60000.
Note. If any RTU devices are polled, set a response time that is long
enough to allow for the normal turn around time from these devices. The
configuration allows for only one setting for all devices connected to the
network.