Paperless recorder 3 Installation
18 OI/RVG200-EN
3.4 Analog / digital input module
3.4.1 Thermocouple
Use the correct compensating cable between the thermocouple and the terminals – see Table 3.1.
Automatic cold junction compensation (ACJC) is incorporated but an independent cold (reference) junction
may be used.
3.4.2 Resistance thermometer (RTD)
On applications requiring long leads it is preferable to use a 3-lead resistance thermometer.
If 2-lead resistance thermometers are used, each input must be calibrated to take account of the lead
resistance.
Note. Tighten analog / digital input terminal screws to a torque of 0.1 Nm (0.9 lbf.in).
Compensating cable
BS1843 ANSI MC 96.1 DIN 43714 BS4937 Part No.30
Thermocouple type + – Case + – Case + – Case + – Case
Ni-Cr / Ni-Al (K) Brown Blue Red Yellow Red Yellow Red Green Green Green White Green *
Ni-Cr / Cu-Ni (E) – – – Violet White Violet *
Nicrisil / Nisil (N) Orange Blue Orange Orange Red Orange – Pink White Pink *
Pt / Pt-Rh (R and S) White Blue Green Black Red Green Red White White Orange White Orange *
Pt-Rh / Pt-Rh (B) – – – Grey White Grey *
Cu / Cu-Ni (T) White Blue Blue Blue Red Blue Red Brown Brown Brown White Brown *
Fe / Con (J) Yellow Blue Black White Red Black Red Blue Blue Black White Black *
* Case Blue for intrinsically safe circuits
Fe / Con (DIN 43710) – –
DIN 43710
–
Blue /
red
Blue Blue
Table 3.1 Thermocouple compensating cable