ScreenMaster RVG200
Paperless recorder 7 Configuration
122 OI/RVG200-EN
Note. The following parameters are displayed only if Implementation is set to Master.
Poll Rate (ms) Set the poll rate in milliseconds minimum 0, maximum 3600000.
Poll fail limit Set the number of successive polls permitted to fail before the data is
marked as a failed input minimum 0, maximum 4.
Response
Timeout (ms)
Set the timeout time in milliseconds for a single poll minimum 0,
maximum 60000.
Note. If any RTU devices connected through a gateway are polled, set a
response time that is long enough to allow for the normal turn around time
from these devices. The configuration allows for only one setting for all
devices connected to the network.