Installation Locations
82 7705 SAR-M Chassis Installation Guide
Passively Cooled Variants
Allow at least 1.75 in. (4.3 cm) clearance above and below and at least 2 in. (5.1 cm) clearance
on the sides of the chassis for proper air flow. Allow at least 2.5 in (6.4 cm) at the front of the
chassis for cable management. The clearances are shown in Figure 16 and described in
Table 12.
Figure 16: Chassis Clearance Specifications (Passively Cooled Variants)
Table 12: Chassis Clearance Specifications (Passively Cooled Variants)
Key Description
1 Front: 2.5 in. (6.4 cm) required for cable management
2 Rear: No clearance required
3 Side: 2 in. (5.1 cm) minimum required for airflow
4 Rack upright: a channel enclosure of 5 in. (12.7 cm) maximum is required for
airflow
5 Top and bottom: 1.75 in. (4.3 cm) required for airflow