7705 SAR-M Ports
164 7705 SAR-M Chassis Installation Guide
External Alarms Port
The External Alarms port provides access to three pairs of alarm output contacts and four 
alarm inputs. All alarm interfaces are rated for 5 VDC and 100 mA (source or sink). Each 
alarm input can be configured with the following:
•name
• description
• administrative state (shut down or not shut down)
• detect and clear debounce timers
• normal conditions (normally open or normally closed)
• association with up to four user-defined alarms
The alarm inputs must be associated with an alarm in order for them to be triggered.
Refer to the 7705 SAR OS Interface Configuration Guide, “Configuring Auxiliary Alarm 
Card and Chassis External Alarm Parameters”, for information on configuring the alarm 
inputs.
You can display the status of the alarm inputs using the show>external-alarms> 
input CLI command. Refer to the 7705 SAR OS Interface Configuration Guide for 
examples of the alarm inputs display.
As well as configuring alarm inputs for settings such as alarm severity, the pins on the 
external alarms connector can also be configured to trigger a log event with a configurable 
severity. For information on configuring the log events on the pins, refer to the 7705 SAR OS 
System Management Guide, “Event Control.” To display the status of the log events, use the 
show>chassis>environment command (see the 7705 SAR OS Basic System 
Configuration Guide).
The port uses an HD-15 female connector. You must provide an appropriate cable configured 
according to your alarm panel. Shielded cable must be used to maintain EMC compliance.
Figure 41 shows the External Alarms port pin numbers.