Installing the Chassis
Page 84 7705 SAR-8 Installation Guide
Before you begin, verify that:
• the equipment rack is securely installed, anchored, and grounded. Refer to the rack
manufacturer’s documentation for instructions.
• the power to the rack is OFF
Required tools:
• a torque driver for Phillips screws
To install the chassis in the rack:
Step 1. Lift the 7705 SAR-8 from the bottom and position it in the rack. If two people are
installing the chassis, position one person in front of the rack and one behind it.
Step 2. Align the mounting holes on each bracket with the mounting holes on the rack rail.
Insert a screw into each mounting hole and tighten.
Step 3. Ground the chassis to the building ground. See Chassis Ground Wiring.