Installing the Components
7705 SAR-8 Installation Guide Page 107
b) Alternatively, the panel may be grounded to the rack through its mounting screws
while adhering to the following requirements.
All surfaces that are used for intentionally grounding the panel must be brought
to a bright finish, and an antioxidant solution must be applied to the surfaces
being joined.
Non-conductive coatings (such as lacquer and enamel) must be removed from
threads and other contact surfaces to ensure electrical conductivity. Thread-
forming screws with paint piercing washers may be used for this purpose during
installation.
Disconnecting a 1.0/2.3 Mini-Coaxial Cable from a
Distribution Panel
Some installations have the 1.0/2.3 Mini-Coaxial Distribution panel installed with no rack
space between the equipment above and below the panel. This type of installation may
require the use of a disconnection tool to facilitate the removal of a mini-coaxial cable.
Figure 30 shows the tool (top and side views). Figure 31 illustrates the use of the tool, which
is shipped with the distribution panel.
Tool required:
disconnection tool for 1.0/2.3 mini-coaxial connectors (supplied with panel)
Figure 30: Mini-Coaxial Connector Disconnection Tool
Figure 31: Disconnecting a 1.0/2.3 Mini-Coaxial Cable from a Distribution Panel
20008
19447