Installing the Components
7705 SAR-8 Installation Guide Page 109
Managing Cable Connections to Adapter Cards
All cable connections to adapter cards are made from the front of the 7705 SAR-8. The
adapter cards can be connected using Ethernet, copper, or fiber-optic cables. A distribution
panel is needed to make coaxial cable connections. Refer to the appropriate adapter card
installation guide for details on connecting to a specific adapter card.
Warnings and Notes
Notes:
Alcatel-Lucent recommends leaving at least 1 RU of space above and/or below the
7705 SAR-8 to run cables from the faceplate connectors. It is not necessary for the space
to be immediately above or below the 7705 SAR-8.
Ensure cables are dressed such that they do not impede the insertion or removal of field-
replaceable units (FRUs), such as CSMs, adapter cards, and the Fan module.
Ensure cables are dressed such that they do not impede viewing the LEDs on the Fan
module.
Typically, cables are routed between the rack uprights.
To maintain EMC compliance, cables that are shielded and grounded at both ends must
be used with the adapter card interfaces.
To meet surge protection requirements, the cable shield must be grounded by attaching
the shield to a convenient chassis ground point, using hardware suitable to provide a
solid electrical and mechanical connection. In addition, ensure that there is sufficient
strain relief to remove any mechanical strain on the ground connection due to cable
movement.
Danger: Only trained and qualified personnel should install or replace this equipment.
Warnings:
Electrostatic discharge (ESD) damage can occur if CSMs or adapter cards are
mishandled. Always wear an ESD-preventive wrist or ankle strap connected to a nearby
ground point that is connected to a site grounding point (typically, the grounding stud on
the 7705 SAR-8, or a properly grounded rack or work bench).
Invisible laser radiation can be emitted from the adapter card aperture ports when no
cable is connected. Avoid exposure and do not stare into open apertures.
Do not power up a 7705 SAR-8 before verifying that all common equipment (chassis,
power, cooling, and grounding) is connected properly and that the fan module and all
cards in the chassis have the same voltage type.
Use only approved small form-factor pluggable (SFP) fiber-optic devices in adapter card
ports.